Appendix RIA45
60 Endress+Hauser
Signal range
Navigation
Setup → Analog in 1/Analog in 2 → Signal range
Description Configures the input signal. Which options are available for selection
depends on the "Signal type" set.
Options 4-20mA, 4-20mA squar, 0-20mA, 0-20mA squar
0-10V, 0-10V squar, 0-5V, 2-10V, 1-5V, 1-5V squar, 0-1V, 0-1V squar,
+/- 1V, +/- 10V, +/- 30V, +/- 100mV
Pt46GOST, Pt50GOST, Pt100IEC, Pt100JIS, Pt100GOST, Pt500IEC,
Pt1000IEC, Ni100DIN, Ni1000DIN, Cu50GOST, Cu53GOST, Cu100GOST,
3000 Ohm
Typ B, Typ J, Typ K, Typ N, Typ R, Typ S, Typ T, Typ C, Typ D, Typ L, Typ L
GOST, Typ U
Factory setting 4-20mA, 0-10V, Pt100IEC, Typ J; depending on the selected input signal
Lower range
Navigation
Setup → Analog in 1/Analog in 2 → Lower range
Description Configures the measuring range lower limit
User entry Numerical value
1)
Factory setting 0
Additional information Only displayed if "Signal type" = "Current" or "Voltage" is set.
Upper range
Navigation
Setup → Analog in 1/Analog in 2 → Upper range
Description Configures the measuring range upper limit
User entry Numerical value
1)
Factory setting 100
Additional information Only displayed if "Signal type" = "Current" or "Voltage" is set.
Connection
Navigation
Setup → Analog in 1/Analog in 2 → Connection
Description Configures the connection type for RTD thermometers
Options 2-wire
3-wire
4-wire
Factory setting 2-wire
Additional information layed if "Signal type" = "RTD" is set.
Tag
Navigation
Setup → Analog in 1/Analog in 2 → Tag
Description Channel name; TAG i the device designation for channel 1
User entry Customized text, max. 12 digits