Appendix RIA45
70 Endress+Hauser
Description Configures the failsafe mode.
Options Invalid
Fixed value
Factory settings Invalid
Additional information Invalid: an invalid value is output in the event of an error.
Fixed value: a fixed value is output in the event of an error.
Fixed fail value
Navigation
Expert → Input → Analog in 1/Analog in 2 → Fixed fail value
Description The value configured here is output in the event of an error.
User entry Numerical value
1)
Factory setting 0
Additional information Only visible if "Fixed value" was selected for the "Failure mode".
Namur NE 43
Navigation
Expert → Input → Analog in 1/Analog in 2 → Namur NE 43
Description Setting as to whether the failsafe mode is in accordance with NAMUR NE
43.
Options On
Off
Factory setting On
Open circ detect
Navigation
Expert → Input → Analog in 1/Analog in 2 → Open circ detect
Description Sets cable open circuit detection.
Options On
Off
Factory setting On
Additional information Only visible if "1-5 V" is configured as the signal range.
Failure delay
Navigation
Expert → Input → Analog in 1/Analog in 2 → Failure delay
Description Delay time for failure in s
User entry Integer value (0-99)
Factory setting 0
Allow reset
Navigation
Expert → Input → Analog in 1/Analog in 2 → Allow reset