RIA45 Appendix
Endress+Hauser 71
Description Setting as to whether saved min./ max. values can be reset in the Display
menu without having to enter a user code which may already have been
configured.
Options No
Yes
Factory setting No
Submenu "Output"
Navigation
Expert → Output
Submenu "Analog Out 1"/"Analog Out 2"
Navigation
Expert → Output → Analog Out 1/Analog Out 2
Description Settings for the analog outputs.
Additional information The following parameters are available for the analog output 1 and analog
output 2.
Failure mode
Navigation
Expert → Output → Analog Out 1/Analog Out 2 → Failure mode
Description Configures the failsafe mode.
Options Min
Max
Fixed value
Factory setting Min
Additional information Min: the saved minimum value is output in the event of an error.
Max: the saved maximum value is output in the event of an error.
Fixed value: a fixed value is output in the event of an error.
Fixed fail value
Navigation
Expert → Output → Analog Out 1/Analog Out 2 → Fixed fail value
Description The value configured here is output in the event of an error.
User entry Numerical value
1)
Factory setting 0
Additional information Only visible if "Fixed value" was selected for the "Failure mode".
Submenu "Relay 1"/"Relay 2"
Navigation
Expert → Output → Relay 1/Relay 2
Description Settings for the relays.
Additional information The following parameters are available for relay 1 and relay 2.
Time delay
Navigation
Expert → Output → Relay 1/Relay 2 → Time delay