EasyManua.ls Logo

Endress+Hauser RMS621 - Extension Card and Remote Display Wiring

Endress+Hauser RMS621
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RMS621 Wiring
Endress+Hauser 19
4.2.4 Extension card connection
Fig. 13: Extension card with terminals
Terminal assignment of Universal extension card
Terminal assignment of temperature extension card
Terminal (item no..) Terminal assignment Slot Input and output
182 24 V sensor power supply 1 B, C, D top, front (B I, C
I, D I)
Current/PFM/pulse input 1
181 Sensor power supply ground 1
112 + 0/4 to 20 mA/PFM/pulse input 1
111 Ground for 0/4 to 20 mA/PFM/pulse input
183 24 V sensor power supply 2 B, C, D top, rear (B II, C
II, D II)
Current/PFM/pulse input 2
181 Sensor power supply ground 2
113 + 0/4 to 20 mA/PFM/pulse input 2
111 Ground for 0/4 to 20 mA/PFM/pulse input
142 Relay 1 Common (COM) B, C, D bottom, front (B
III, C III, D III)
Relay 1
143 Relay 1 normally open (NO)
152 Relay 2 Common (COM) Relay 2
153 Relay 2 normally open (NO)
131 + 0/4 to 20 mA/pulse output 1 B, C, D bottom, centre (B
IV, C IV, D IV)
Current/pulse output 1 active
132 - 0/4 to 20 mA/pulse output 1
133 + 0/4 to 20 mA/pulse output 2 Current/pulse output 2 active
134 - 0/4 to 20 mA/pulse output 2
135 + pulse output 3 (open collector) B, C, D bottom, rear (B V,
C V, D V)
Passive pulse output
136 - pulse output 3
137 + pulse output 4 (open collector) Passive pulse output
138 - pulse output 4
Terminal (item no..) Terminal assignment Slot Input and output
117 + RTD power supply 1 B, C, D top, front (B I, C
I, D I)
RTD input 1
116 + RTD sensor 1
115 - RTD sensor 1
114 - RTD power supply 1

Table of Contents