RMS621 Commissioning
Endress+Hauser 31
6.3.3 Main menu - Setup
The Setup menu is used for configuring the Energy Manager. The following subsections and tables
list and describe all the configuration parameters of the Energy Manager.
Procedure when configuring the Energy Manager
1. Select system units (device settings).
2. Configure inputs (flow, pressure, temperature), i.e. assign terminals to the sensors and scale
the input signals, if necessary configure default values for pressure and temperature.
3. Select application (e.g. steam mass/heat).
4. Configure application, i.e. assign the configured inputs (sensors) .
5. Configure outputs (analog, pulse or relay/limit values).
6. Check display settings (values are preset automatically).
7. Make optional device settings (e.g. communication settings).
"
Caution!
If you change configuration parameters, check whether this has an affect on other parameters and
your overall measuring system.
Set-up Basic set-up
!
Note!
Factory settings are indicated in bold.
The basis data of the device are defined in this submenu.
Function (menu item) Parameter setting Description
Date-Time
Date DD.MM.YY
MM.DD.YY
For configuring the current date (country-specific).
!
Note!
Important for summertime/wintertime changeover
Time SS:MM Current time for the real time clock of the device.
Summertime/normal time changeover
Changeover Off - Manual - Auto. Kind of time changeover.
Region Europe - USA Displays the changeover date from normal time (NT) to
summertime (ST) and vice versa. This function depends on the
region selected.
•NTÆST
STÆNT
–Date
–Time
31.03 (Europe)
07.04 (USA)
27.10 (Europe
27.10 (USA)
02:00
Takes into consideration the summertime/normal time
changeover in Europe and USA at different times. This can
only be selected if summertime/normal time changeover is not
set to ’Off’.
Time of changeover. This can only be selected if summertime/
normal time changeover is not set to ’Off’.
System eng. units
System eng. units Metric
American
Random
Sets the unitary system. "Random" means that a picklist with
different unitary systems, incl. time basis and format, appears
in the individual operating items.
Code
•User
Alarm lim.
0000 - 9999
0000 - 9999
Device operation is only enabled once the previously defined
code has been entered.
Only the alarm limits are enabled for configuration. All other
parameters remain locked.