RMS621 Trouble-shooting
Endress+Hauser 55
9.3 Process error messages
Display Cause Remedy
Config error:
Pressure
Analog temperature
Temperature RTD sensor
•Analog flow!
PFM pulse flow!
Applications!
Limit values!
•Analog outputs!
Pulse outputs!
Pressure mean value
Temperature mean value
Flow mean value
Flow differential pressure (DP)
Flow splitting range
Flow DP: no computation
Incorrect or incomplete programming or loss of
calibration data
Contradictory terminal assignment
Error in computation
No computation takes place due to the incorrect
configuration
Check whether all necessary items have been
defined with plausible values.
( Section 6.3.3 Main menu - Setup)
Check whether there is contradictory input
assignment (e.g. flow 1 assigned to two
different temperatures).
( Section 6.3.3 Main menu - Setup)
Wet steam alarm The steam status calculated from the temperature
and pressure is near
(2 °C / 3.6 °F) the saturated steam curve
Check the application, devices and connected
sensors.
Change the limit function if you do not need the
“WET STEAM ALARM”.
( Set point settings, Section 6.3.3)
Temp. outside steam range! Measured temperature outside the permitted
steam value range. (0 to 800 °C (32 to 1472 °F))
Check settings and connected sensors.
( Input settings, Section 6.3.3)
Pressure outside steam range! Measured pressure outside the permitted steam
value range. (0 to 1000 bar (0 to 14504 psi))
Check settings and connected sensors.
( Input settings, Section 6.3.3)
Temperature exceeds sat. steam range! Measured or calculated temperature outside the
saturated steam range (T>350 °C (662 °F))
Check settings and connected sensors.
Set "superheated“ steam and carry out
measurement task with three input variables
(Q, P, T).
( Application settings, Section 6.3.3)
Steam: condensate temperature Phase transition!
Measured or calculated temperature corresponds
to condensate temperature of the saturated steam.
Check application, devices and connected
sensors.
Measures for process control: increase
temperature, reduce pressure.
Possibly imprecise temperature or pressure
measurement; purely computed transition from
steam to water which does not really occur.
Compensate inaccuracies by setting an
offset for temperature (approx. 1-3 °C (1.8-
5.4 °F)).
Water: boiling temperature Measured temperature corresponds to the boiling
temperature of the water (water evaporates!)
Check application, devices and connected
sensors.
Measures for process control: reduce
temperature, increase pressure.
Signal range error "channel name" "signal name" Current output signal below 3.6 mA or above
21 mA.
Check whether the current output is scaled
correctly.
Change the start and/or end value of the
scaling