Commissioning RMS621
46 Endress+Hauser
Setup → Outputs
Analog outputs
Please note that these outputs can be used as both analog and pulse outputs; the desired signal type
can be selected for each setting. Depending on the version (extension cards), 2 to 8 outputs are
available.
Function (menu item) Parameter setting Description
Identifier Anal. outp. 1 to 8 An identifier can be given to the analog output in question for a
better overview (max. 12 characters).
Terminals B-131, B-133
C-131, C-133
D-131, D-133
E-131, E-133
None
Defines the terminal at which the analog signal should be
output.
Sig. source Density 1
Enthalpy 1
Flow 1
Mass flow 1
Pressure 1
Temperature 1
Heat flow 1
Select
Setting as to which calculated or measured variable should be
output at the analog output. The number of signal sources
depends on the number of configured applications and inputs.
Curr. range 4 to 20 mA, 0 to 20 mA Specifies the mode of operation of the analog output.
Start value -999999 to 999999
0.0
Smallest output value of the analog output.
End value -999999 to 999999
100
Largest output value of the analog output.
Time const. (signal
damping)
0 to 99 s
0 s
Time constant of the first order low pass for the input signal.
This is used to prevent large fluctuations in the output signal
(can only be selected for the signal type 0/4 and 20 mA).
Fault cond. action Minimum
Maximum
Value
Last value
Defines the behaviour of the output in the event of a fault, e.g.
if a sensor in the measurement fails.
Value -999999 to 999999
0.0
Fixed value which should be output at the analog output in the
event of a fault.
!
Note!
Only for the Fault cond. action setting; value can be selected.
Simulation 0 - 3.6 - 4 - 10 - 12 - 20 -
21
Off
The function of the current output is simulated. Simulation is
active if the setting is not ’off’. Simulation ends as soon as you
leave this item.