Commissioning RMS621
28 Endress+Hauser
6 Commissioning
6.1 Function check
Make sure that all post-connection checks have been carried out before you commission your
device:
See Section 3.3 ’Post-installation check’
Checklist Section 4.3 ’Post-connection check’
6.2 Switching on the measuring device
6.2.1 Basic unit
Once the operating voltage is applied, the green LED (= device operating) lights up if no fault is
present.
When the device is first commissioned, the prompt "Please set up device" appears on the display.
Program the device as per the description Chap. 6.3.
When commissioning a device already configured or preset, measuring is immediately started as
per the settings. The values of the display group currently set appear on the display. By pressing
any key, you get to the navigator (quick start) and from there back to the Main menu
(see Section 6.3).
6.2.2 Extension cards
When the operating voltage is applied, the device automatically recognises the installed and wired
extension cards. You can now follow the prompt to configure the new connections or perform the
configuration at a later date.
6.2.3 Remote display and operating unit
The remote display/operating unit is preconfigured at the factory - device address 01, baudrate
56.7k, RS485-Master. Once the supply voltage has been applied and after a short initialisation
period, the display unit automatically starts communication to the connected basic unit. Make sure
that the device address of the basic unit and of the remote display match.
Fig. 21: Start Setup menu
You can get to the Setup menu of the display/operating unit by pressing the left and right top key
at the same time for 5 seconds. Here, the baudrate and device address for communication, as well
as the contrast and display viewing angle can be configured. Press ESC to exit the Setup menu of
the display/operating unit and to get to the display window and the Main menu to configure the
Energy Manager.
!
Note!
The Setup menu for configuring the basic settings of the display/operating unit is only available in
English.