RMS621 Commissioning
Endress+Hauser 47
Pulse outputs
The pulse output function can be configured with active, passive output or relay. Depending on the
version, 2 to 8 pulse outputs are available.
Function (menu item) Parameter setting Description
Identifier Pulse 1 to 8 An identifier can be assigned to the pulse output in question for
a better overview (max. 12 characters).
Signal Active
Passive
Relay
Select
Assign the pulse output.
Active: Active voltage pulses are output. Power is supplied
from the device.
Passive: Passive open collectors are available in this operating
mode. Power must be supplied externally.
Relay: The pulses are output on a relay. (The frequency is
max. 5Hz)
!
Note!
"Passive" can only be selected when extension cards are used.
Terminals B-131, B-133, C-131, C-
133, D-131, D-133, E-
131, E-133
B-135, B-137, C-135, C-
137, D-135, D-137
A-52, B-142, B-152,
C-142, C-152, D-142, D-
152
None
Defines the terminal at which pulses should be output.
Sig. source Heat sum 1, Heat sum 2,
Flow sum 1, Flow sum 2,
etc.
Select
Setting as to which variable should be output at the pulse
output.