Trouble-shooting RMS621
56 Endress+Hauser
Cable open circuit: "channel name" "signal name) Input current at current input smaller than 3.6 mA
(with setting 4 to 20 mA) or larger than 21 mA.
Incorrect wiring
Sensor not set to 4–20 mA range.
Sensor malfunction
Incorrectly configured end value for flow
transmitter
Check sensor configuration.
Check function of the sensor.
Check end value of the connected flow meter.
Check wiring.
Range error 3.6 mA < x < 3.8 mA
(with setting 4 to 20 mA) or
20.5 mA < x < 21 mA
Incorrect wiring
Sensor not set to 4–20 mA range.
Sensor malfunction
Incorrectly configured end value for flow
transmitter
Check sensor configuration.
Check function of the sensor.
Check measuring range/scaling of the
connected flow meter.
Check wiring.
Cable open circuit: "channel name" "signal name Resistance too high at PT100 input, e.g. due to
short-circuit or cable break
Incorrect wiring
PT100 sensor defect
Check wiring.
Check function of the PT100 sensor.
Temp. difference range undercut Range of the set differential temperature overshot Check current temperature values and set
minimum temperature differential.
Limit value over/under cut
Limit value ’number’ ok (blue)
"Limit value identifier" < "threshold value"
"unit"
"Limit value identifier" > "threshold value"
"unit"
"Limit value identifier" > "gradient" "unit"
"Limit value identifier" < "gradient" "unit"
"User defined message"
Limit value undershot or overshot
( Set point configuration, Section 6.3.3)
Acknowledge alarm if the function “Set point/
Lim. display/Disp.+Ackn.“ was configured
( Set point configuration, Section 6.3.3).
Check application if necessary.
Adjust set point if necessary.
Temp. difference range undercut (red)
Temp. difference ok (blue)
Range of set differential temperature overshot. Check current temperature values and set
minimum temperature differential.
W-heat diff: error: neg. temp. diff. The temperature assigned to the temperature
sensor on the cold side is larger than the
temperature on the warm side.
Check whether the temperature sensors are
correctly wired.
Adjust process temperatures.
W-heat diff: error flow direction In bidirectional water-heat-diff. operation;
If flow direction is configured as changing and the
direction of flow does not suit the temperature
values.
Change flow direction signal at the direction
terminal.
Check the wiring of the temperature sensors.
Pulse width must be between 0.04 and
1000 ms!
Pulse width must be between 100 and
1000 ms!
Active/passive pulse output: configured pulse
width not within valid range.
Change the pulse width to the value range given.
Entry must lie between 1 and 15! Incorrect number of points. Correct value to a value in this value range.
Pulse buffer overflow Too many pulses accumulated so the pulse counter
overflows: pulses lost.
Increase pulse factor
Other messages/events (only appear in the event buffer)
Low flow: undershot! Low flow cut off configured is undershot, i.e. flow
valued at zero.
Reduce low flow cut off if necessary. (see Section
6.3.3)
Display Cause Remedy