Expan. coeff. 0 to 9.9999e-XX Correction factor for compensating the temperature effect on
the flow transmitter. This factor is often indicated on the
nameplate for vortex flowmeters, for example. If no value is
known for the expansion coefficient or if this has already been
compensated by the device itself, please set 0 here.
Default: 4.88e-05
!
Note!
Note! Only active if correction setting is active.
Table Use
Not used
If the flow curve of your transmitter deviates from the ideal
pattern (linear or square root), this can be compensated by
entering a correction table.
For details, see the 'Correction tables' in Section 11.2.1.
No. of rows 01 - 15 Number of points in the table.
Corr. tab. pulse Point (used/delete)
Current/flow frequency/
k-factor
If the flow curve of your transmitter deviates from the ideal
pattern (linear or square root), this can be compensated by
entering a correction table. The parameters in the table depend
on the flow transmitter selected.
• Analog signal, linear curve
Up to 15 value pairs (current/flow)
• Pulse signal, linear curve
Up to 15 value pairs (frequency/k-factor or frequency/pulse
value).
For details, see the 'Correction tables' in Section 11.2.1.
Sums Unit
Format
Total
Signal reset
Terminals
Possibility of configuring or resetting the totalizers for the
volume flow. Signal reset, i.e. resetting the totalizer by an
input signal (e.g. remote read-out of totalizers with subsequent
reset).
(Terminal for this input signal only active if "Signal Reset =
YES")
Alarm response
Range violation
Open circuit
Alarm type
Colour change
Fault text
For this input, individually specify which alarms should be
displayed when faults occur: range violation (as per
NAMUR43) or open circuit.
!
Note!
Only active if the option Random was selected in the 'Alarm
response' menu item in Setup Æ Basic set-up.
Alarm type Fault
Hint
Fault message, totalizer stop, colour change (red) and message
in plain text.
Colour change Yes
No
Select whether the alarm should be signalled by a colour
change from blue to red.
!
Note!
Only active if the ’Hint’ alarm type has been selected.
Fault text Display+acknowledge
Do not display
Select whether an alarm message should appear to describe the
fault when a fault occurs. This is cleared (acknowledged) by
pressing a key.
!
Note!
Only active if the ’Hint’ alarm type has been selected.
Function (menu item) Parameter setting Description