Technical data RMS621
62 Endress+Hauser
Max. number:
• 8 x 0/4 to 20 mA/pulse (depends on the number of extension cards)
• 6 x digital passive (depends on the number of extension cards)
Signal sources
All available multifunctional inputs (current, PFM or pulse inputs) and results can be freely allocated
to the outputs.
Switching output Function
Limit relay switches in the operating modes: minimum/maximum safety, gradient, alarm, saturated
steam alarm, frequency/pulse, device error
Switch behaviour
Binary, switches when the limit value is reached (potential-free NO contact)
Relay switching capacity
Max. 250 V AC, 3 A / 30 V DC, 3 A
!
Note!
A mixture of low voltage and extra-low voltage is not permitted for the relays of the extension cards.
Switching frequency
Max. 5 Hz
Threshold
Freely programmable (wet steam alarm is preset at 2 °C (3.6 °F) at the factory)
Hysteresis
0 to 99%
Sig. source
All available inputs and calculated variables can be allocated freely to the switching outputs.
Number
1 (in the basic unit)
Max. number: 7 (depends on the number and type of extension cards)
No of output states
100,000
Scan rate
500 ms