Electrical Characteristics
Symbol Parameter Conditions Min Max Units
V
I
Input Voltage Analog measuring range 0,0 5,0 V
I
I
Input Current Analog measuring range 0,0 22,7 mA
V
IH
Input High Voltage
(Note 1) 2,0 30 V
(Note 2) 2,0 15 V
V
IL
Input Low Voltage -0,5 1,0 V
I
IH
Input High Current (Note 2) 9,0 27 mA
I
IL
Input Low Current (Note 2) -2,3 4,5 mA
R
I
Input Resistance
Referred to 2,5 V (Note 1) 40 42
k
Ω
(Note 2) 215 225
Ω
TIRE
Total Input Referred
Error
0,25 V
(Note 2) 1,1 mA
π
I
Time Constant of Input
Low Pass Filter
(Note 1) 3,1 4,7 ms
Connection Principle; High Impedance Voltage Input
Connection Principle; Low Impedance Current Iinput
Note 1: Input Configured for Voltage Measurement (220 Ω Input Resistor Disconnected)
Note 2: Input Configured for Current Measurement (220 Ω Input Resistor Connected)
+24V
Module
"0"
+24V
Module
"1"

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Epec 2024 and is the answer not in the manual?

Epec 2024 Specifications

General IconGeneral
BrandEpec
Model2024
CategoryControl Unit
LanguageEnglish

Related product manuals