EVCO | 06.08.2021 | AZ | 16
12
ON
c-pro 3 OEM
USB
2
1
ON
AO4AO3 AO2AO1 D14 D13 IN7IN6 IN5 IN4 IN3IN2 IN1 GND 12VS IB GND A+ B- CAN+ CAN-5VS
C01 NO1 C02 NO2 C03 NO3 C04 NO4 C05 NO5NO6 C06 NC6 DIHV1DIHV1 DIHV2 DIHV2 AC AC
K1
++ +
INTRA
BUS
RS-
485
CAN
GND
Data
GND
+
-
GND
+
-
K2 K3 K4 K5 K6
Max. 12 A
DIHV5 DIHV5
IN OUT
Pulse - EPB9BVE
114CP3OEE104
c-pro 3 OEM - Hardware manual
Plastic housing version (blind/LCD)
Termination of the RS-485 MODBUS and CAN networks.
Polarisation of RS-485 MODBUS network
To terminate the RS-485 MODBUS network:
– Place the micro-switch 1 in position ON
To terminate the CAN network:
– Place the micro-switch 2 in position ON
The RS-485 MODBUS network can be polarised using the
UNI-PRO 3 development environment.
Analog output 4
Digital output 1
Power supply
(115... 230 VAC)
Digital input 1
Digital input 2
Digital output 4
Digital output 2
Digital output 5
Digital output 3
Digital output 6
Analog output 3
Analog output 2
Analog output 1
Digital input 4
Digital input 3
Analog input 7
Analog input 6
Analog input 5
Analog input 4
Analog input 3
Analog input 2
Analog input 1
USB
cable
PC with
UNI-
PRO 3
BMS
Device
with
INTRABUS
Device
with
CAN port
Electric system
(230 VAC)
Electric system
(230 VAC)
Mains supply
(115... 230 VAC)
Neutral
Pulse
valve
Phase
Digital input 5