EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204
page 54 of 86
Parameters (2)
[ press button
RIGHT to
show it ]
I/O Timeout 1 240 s 60
time-out of the CANbus communication for
the test of the remote values of the I / O
(after this time without CANbus
communication, the I / O of the controller is
disabled)
Parameters (2)
[ press button
RIGHT to
show it ]
En. Prg Level - - - - - - - - - NO
enabling the access to the first level page
pressing a combination of buttons
YES = yes, operating as follows:
- keep pressed 3 s button
ENTER to gain access
to the first page of
level 1
- keep pressed 3 s
buttons ENTER and
ESC to gain access to
the first page of level 2
- keep pressed 3 s
buttons LEFT and
RIGHT to gain access to
the first page of level 3
Parameters (2)
[ press button
RIGHT to
show it ]
Password Indi - - - - - - - - - NO
connection among the passwords to gain
access to the levels
NO = one has not to set any
password to gain access to
levels lower than the one one
has already gained access
YES = one has to set a password to
gain access to each level
Parameters (2)
[ press button
RIGHT to
show it; not
available in the
blind versions ]
Backlight - - - - - - - - - TIME
kind of backlight
OFF = the backlight is never lit
ON = the backlight is always lit
TIME = the backlight is lit the time one
has set with parameter
B. Time since the last
operation with the buttons
Parameters (2)
[ press button
RIGHT to
show it; not
available in the
blind versions ]
B. Time 0 60 s 240
backlight duration (only if parameter
Backlight has value TIME)