EVCO S.p.A. c-pro 3 | Hardware manual ver. 2.0 | Code 114CP3E204
page 57 of 86
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
BTR(1) 1 15 - - - 15 reserved
Networks / BMS
(4)
MAC ID -1 127 - - - -1
local (or of the controller) BACnet MS/TP
node address
-1 = not enabled
Networks / BMS
(4)
Baud Rate - - - - - - - - - 19200
BACnet MS/TP communication baud rate
9600 = 9,600 baud
19200 = 19,200 baud
38400 = 28,000 baud
76800 = 76,800 baud
Networks / BMS
(4)
Max Master 0 127 - - - 127
maximum number of master in a BACnet
MS/TP network
Networks / BMS
(4)
Max InfoFram 1 127 - - - 3
maximum number of packages transmitted
as master before giving the token
Networks / BMS
(4)
Device ID 1 4194303 - - - 108 identity in a BACnet MS/TP multinetwork
Networks /
UART1
(1)
Address 1 247 - - - 1
local (or of the controller) Modbus node
address in a RS-485 network wired on the
first RS-485 port
Networks /
UART1
(1)
Baud Rate - - - - - - - - - 9600
Modbus communication baud rate in a
RS-485 network wired on the first RS-485
port
1200 = 1,200 baud
2400 = 2,400 baud
4800 = 4,800 baud
9600 = 9,600 baud
19200 = 19,200 baud
28800 = 28,000 baud
38400 = 38,400 baud
57600 = 57,600 baud
Networks /
UART1
(1)
Parity - - - - - - - - - EVEN
Modbus communication parity in a RS-485
network wired on the first RS-485 port
NONE = no parity
ODD = odd
EVEN = even