EasyManua.ls Logo

Evco EV3 200 WEB - Defrost When Compressor Stops

Evco EV3 200 WEB
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1143W24E4.00 · EV3 200 Web 03/2021
| 26 |
6.3.3 Defrost when compressor stops
Defrost when the compressor stops is obtained by setting d1 = 2.
The defrost configuration parameters with cycle reversed are:
Par. Description MU Range
d0 Defrost interval. h 0...99
d1
Type of defrost.
0 = Electrical heaters;
1 = Cycle reversed (hot gas);
2 = When compressor stops.
--- 0...2
d3 Defrost duration. min 0...99
d7 Evaporator dripping time after defrost. min
0...15
Pb3
ON
OFF
d2
ON
OFF
d3
d7
Defrost
request
End of
defrost
Fig. 26. Defrost with cycle reversed - End of defrost due to maximum time

Table of Contents

Other manuals for Evco EV3 200 WEB

Related product manuals