10. DIAGNOSTICS
Thetablebelowlistsalarmswiththeircorrespondingsolutions.Tosignalanalarm,theLEDalarmlightsup and the buzzer
sounds.EveryalarmisrecordedintheAlarmmenu.
10.1 TABLE OF ALARMS
Code Description Cause Effects Resolution
Pr1
Probe error
Probenotworking
Probe incorrectly
connected
Incorrect type of probe
Code Pr1 displayed
AlarmoutputON
Compressor regulated according
to C4 and C5
Defrost suspended
Checkthetypeofprobe(PO)
Checkprobewiring
Change type of probe
Pr2
Code Pr2 displayed
AlarmoutputON
If P4=1,defrostactivefortimed3
Pr3
Code Pr3 displayed
No effect on regulation
rtc Clockalarm
Clock(RTC)alarmnot
working
Clock-connectedfunctionsnot
present or not synchronised with
the actual time
Set the right time.
Iftheerrorpersists,replacethe
device (RTC battery dead)
AL
Lowtemperature
alarm Pb1
Temperature Pb1 > A1 for
a time equal to A7
Code AL displayed
No effect on regulation
Wait until the temperature read by
Pb1 goes below the alarm threshold
(A1-A11)
AH
High
temperature
alarm Pb1
Temperature Pb1 > A4 for
a time equal to A7
Code AH displayed
No effect on regulation
Wait until the temperature read by
Pb1 goes above the alarm threshold
(A4+A11)
id Door open alarm
Digital input activated for
a time > i2
Code id displayed
Regulatorsblockeddependingon
the current function in iC1=7,8
or 9
If i2 = -1 the alarm is disabled;
Checki2 and iP1
PF
Power failure
alarm
Power failure for longer
than A10
Code PF is recorded Checkthepowersupplywiring
COH
Condenser
overheat signal
Condenser temperature
> C6
Code COH displayed
No effect on regulation
CheckC6
CSd
High
condensation
alarm
Condenser temperature >
C7 for a time equal to C8
Code CSd displayed
Compressorlocked
Switch the device off then on again;
CheckC7 and C8
iA
Multi-purpose
input alarm
Digital input activated
(iC1 = 2) for a time equal
to i5
Code iA displayed
No effect on regulation
Checki5 and i6
CtH
Compressor
thermal switch
alarm
Digital input activated
(iC1 = 5)
The regulator counts the number of
eventsi8inthetimei7fromtherst
one
If i7 = 0 alarm is always
automatically reset
C
h
ecki5 and i6
th
Thermal switch
global alarm
Digital input activated
(iC1 = 5)
The regulator counts the number of
eventsi8inthetimei7fromtherst
one
Switch the device off then on again;
Checki5 and i6
dFd
Defrost timeout
alarm
Defrost terminated due
to timeout and not to
reaching temperature d2
Code dFd displayed
No effect on regulation
Touchanykey
Checkd2,d3 and d11

Table of Contents

Other manuals for Evco EV3 200 WEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco EV3 200 WEB and is the answer not in the manual?

Evco EV3 200 WEB Specifications

General IconGeneral
BrandEvco
ModelEV3 200 WEB
CategoryController
LanguageEnglish

Related product manuals