1143W24E4.00 · EV3 200 Web 03/2021
| 27 |
7. REGULATORS
7.1 HEATING/COOLING TEMPERATURE
The temperature regulation configuration parameters are:
Par. Description MU Range
r0 Cooling regulation differential; temperature to be added to the setpoint (Setpoint + r0) °C/°F 0.1...25.0
r1 Minimum value attributable to setpoint. °C/°F -30.0...r2
r2 Maximum value attributable to setpoint. °C/°F r1...99.0
r12 Differential position r0. 0=Asymmetrical;1 = Symmetrical. ---
0/1
u7 Neutral zone threshold for heating. °C/°F -99.0...99.0
7.1.1 Operation
The controller manages the temperature according to the type of request (heating/cooling).
°C/°F
Con r5 = 0
r0
Setpoint
Setpoint
°C/°F
Con r5 = 1
Setpoint - u7 + 2°
Fig. 27. Operation of temperature regulator
Cooling
If the controller receives a cooling request:
Cooling output (Compressor) between Setpoint + r0 and Setpoint .
When the temperature read by Pb1 reaches the value of Setpoint + r0,thecontrolleractivatesthecompressoroutputtocool
until the temperature goes below the threshold set by Setpoint.
Heating
If the controller receives a heating request:
Heating output (Heaters) between Setpoint and Setpoint - u7+ 2°.
When the temperature read by Pb1 reaches the value of Setpoint - u7,thecontrolleractivatestheheateroutputtoproduce
heat until the temperature goes above the threshold set by Setpoint - u7 + 2°.
7.2 HEATING/COOLING TEMPERATURE IN THE NEUTRAL ZONE
The temperature regulation configuration parameters in the neutral zone are:
Par. Description MU Range
r0 Cooling regulation differential; temperature to be added to the setpoint (Setpoint + r0) °C/°F 0.1...25.0
r1 Minimum value attributable to setpoint. °C/°F -30.0...r2
r2 Maximum value attributable to setpoint. °C/°F r1...99.0
u7 Neutral zone threshold for heating. °C/°F -99.0...99.0
7.2.1 Operation
Regulation in the neutral zone is activated if r11≠0(ifr11<0,theneutralzoneisactivatedwithaheatingrequest).
Setpoint
°C/°F
Setpoint + r0
Setpoint - u7 + 2°
Setpoint - u7
Fig. 28. Operation of temperature regulator in the neutral zone

Table of Contents

Other manuals for Evco EV3 200 WEB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco EV3 200 WEB and is the answer not in the manual?

Evco EV3 200 WEB Specifications

General IconGeneral
BrandEvco
ModelEV3 200 WEB
CategoryController
LanguageEnglish

Related product manuals