EasyManua.ls Logo

Evco EV3 200 WEB - Page 9

Evco EV3 200 WEB
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1143W24E4.00 · EV3 200 Web 03/2021
| 9 |
Analogue input features
Default
NTC 10 kΩ at 25 °C 
BETA 3435
PTC KTY 81-121
990 Ω at 25 °C
RH Digital input
Pb1
Probe
Temperature
--- --- ---
Pb2
Probe
Evaporator
--- --- ---
Range
---
-40...105 °C
(-40...220°F)
--- --- ---
Resolution
--- 0.1°C(1°F) --- --- ---
Input
impedance
--- 10kΩ --- --- ---
Digital output features
Default Description Load (at 250 Vac) Type of load
Out1 Compressor SPDT 16A Resistive
Out2 AUX SPDT 5A Resistive
Out3 Fans SPDT 5A Resistive
Out4 Not configured SPDT 8A Resistive