Appendix A: Wiring and Breaker Requirement
Inverter wiring
Inverter power terminal (Purchased separately)
1
2
3 8 AWG
No.
90°C(194°F), 600 V, copper
90°C(194°F), 600 V, copper
90°C(194°F), 600 V, copper
0.47 in / 12 mm
10-8 AWG
Cross-sectional Area Range
Strip Length
Terminals
PV terminals
AC terminals
Ground terminals
Type
0.47 in / 12 mm
0.47 in / 12 mm
10-8 AWG