12 Troubleshooting
This section contains information and procedures for solving possible
problems with EVERVOLT Home Battery System, and provides you with troubleshooting
tips to identify and solve most problems that could occur with the system.
This section will help you narrow down the source of the problems you may
encounter. Please read the following troubleshooting steps.
Check warnings or fault messages on the myEVERVOLT Cloud. If a message is displayed,
record it before doing anything further operation.
AFD Self Check
Fault
Arc Detect Fault
PV Conn Dir Fault
PV Reverse Connection Fault
Ÿ Re-connect the PV correctly
BAT Volt Fault
Battery Voltage Over high or Over low Fault
Ÿ Check if the battery input voltage is within the normal range
Ÿ
EPO Fault
EPO Activated or Inverter Emergency Off
BI Comm Fault
Communication Fault between Inverter and BI
Ÿ Check if the RS485 communication cable of BI connects to
communication board of inverter.
Ÿ
DC Arc occurs or DC Arc Check Fault
Ÿ
Please check if there is any visible arc vestige firstly
Ÿ
Clear the PV input and solar battery board connects normally
Ÿ If Arc is detected five times in one hour, please manually clear Arc.
Otherwise, it will re-connect to grid in five minutes
Faults
Diagnosis and solution
AFDI Model Self Check Fault
Please check if the AFDI module connects normally
Or contact Panasonic Technical Support
Troubleshooting for inverter
Indicator Light and Button
105
104
Or contact Panasonic Technical Support
Or contact Panasonic Technical Support
EV-SB power button
When ON, the EVERVOLT Home Battery System can intelligently switch
between on-grid and off-grid without human intervention.
When OFF, manual control of the EV-SB will be enabled when the
internal relay is not switched automatically. When some unrecoverable
failure is encountered, causing the system to stop running and the home
load to lose power, the following operations can be performed:
1. Open the door of the EV-SB.
2. Turn off the breaker between the inverter and the EV-SB, as well as
the breaker between the EV-SB and the generator.
3. Turn off the main breaker on the grid side.
4. Wait for 60s.
5. Press the EV-SB power button to enter manual maintenance mode.
6. Use the tool to turn the left and right relays to ON.
7. Turn on the main breaker to make the grid ready to power the home
load!
8. Turn on the breaker between the inverter and the EV-SB to make the
inverter run again.
9. Close the door of the EV-SB.
Indicator Light and Button
Ÿ
Ÿ
Gen source
disconnect
Grid disconnect