Chapter 4
Extension Cards
4.5.2. Energy Demand Points (Extension Cards)
Each Extension Card requires a certain amount of Energy Demand Points.
The energy demand points per Extension Card type are specified in this guide. Values are
given in the table of #B. Flexy Extension Cards |outline. Examples are given below:
2 Serial Ports
FLA 3301
Single Ethernet
FLX 3101
3G GSM
FLB 3202
Energy Demand Points 1 1 10
Table of the Energy Demand Points for 3 types of Extension Cards
4.5.3. Power Balance Check Example
Considering the configuration shown in the second picture of § #4.1.Base Unit Slot
Compatibility
Energy Points
(max 50°C)
Energy Points
(max 70°C)
Available Energy Base Unit Flexy 201 29 20
Energy Demand 2 Serial Ports Extension FLA 3301 -1 -1
Energy Demand Single Ethernet Extension FLX 3101 -1 -1
Energy Demand 3G GSM Extension FLB 3202 -10 -10
Energy Balance
17 > 0 = OK 8 > 0 = OK