EasyManua.ls Logo

eWON Flexy - Resetting the eWON Flexy; 6.2. First Level Reset (user reset); 6.3. Second Level Reset (factory reset)

eWON Flexy
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6
Resetting the eWON Flexy
6. Resetting the eWON Flexy
The reset button B1 is located on the right side of the Base Unit (see § 3.3.2 Reset Button). The
reset function of this button is active only if pressed while powering on. The eWON Flexy
features two type of reset levels. A table follows with the impacted configuration zones per
reset level.
6.1. Normal Boot Sequence
The normal boot sequence of the eWON Flexy takes approximately 25 seconds to
complete. During this process, all LEDs of the left row are shortly ON, except BI1 as long as
the RESET button is not pressed. During this boot sequence, the USR LED is orange. As soon as
the boot sequence has finished and the unit is ready to be used, the USR LED flashes GREEN
slowly.
6.2. First Level Reset (user reset)
The first level reset consists in formatting only the « user files » part of the non volatile
memory. This type of reset does not modify the communication parameters of the eWON
Flexy.
How do I generate a first level reset?
Power the unit OFF and ON again
Immediately press and maintain the reset button. The LED labeled BI1 turns ON.
Wait approximately 30 seconds until the USR LED flashes RED 1x per second.
Immediately release the button. The LED labeled BI1 turns OFF.
if you wouldn't, you'd reach the second level reset phase.
Wait approximately 30 secs until the reset procedure is completed.
The eWON restarts automatically and the unit is ready to be used, the USR LED flashes
GREEN slowly.
6.3. Second Level Reset (factory reset)
This second level reset formats all non volatile memories and returns the eWON to its factory
defaults. This operation consists in 3 steps:
Formatting of all non volatile memories, including all COM parameters and IP
addresses
Full hardware auto test with result shown by the USR LED
Return to ex-factory configuration (default config)
Page 31 / 40 eWON Flexy - Base Units | IG 014