Chapter 6
Resetting the eWON Flexy
How do I generate a second level reset?
Power the unit OFF and ON again
Immediately press and maintain the reset button. The LED labeled BI1 turns ON.
Wait approximately 35 seconds until the USR LED remains RED steady.
When this state is reached, release the button. The LED labeled BI1 turns OFF.
It takes no longer than 2 seconds to complete.
Check if the auto test is successful, the USR LED flashes RED with a pattern of 200ms ON
and 1,5 sec OFF (*). The eWON Flexy does NOT restart in normal mode by itself and
remains running in this diagnose mode.
You have to power the eWON Flexy OFF and ON again to reboot the unit in normal
mode. As described before, the eWON returns to its default COM parameters and
factory IP addresses (like LAN 10.0.0.53) after this level 2 reset is performed.
(*) Any other pattern reflects a problem. The pattern will start with 200ms ON (beginning of
the pattern) followed by OFF and a certain number of times 1 sec ON allowing to identify
the nature of the detected problem. Please write down the pattern you observed and
contact your distributor if you are confronted with an error pattern on the USR LED.
Page 32 / 40 eWON Flexy - Base Units | IG 014