version 4.7.2 July 10th, 2022 Firmware version V2.1.7 and higher
EXXFIRE Installation and Service Manual 10
2 PRODUCT DESCRIPTION
EXXFIRE
®
750CNF/1500CNF/2250CNF
The EXXFIRE® 750CNF/1500CNF/2250CNF is a unit that is used to detect and extinguish fires in
small protected spaces, such as server racks and electrical cabinets. The EXXFIRE®
750CNF/1500CNF/2250CNF is equipped with:
One, Two or Three Cool Gas Generators (CGG) to release nitrogen gas
Air inlet fan and filter
Three optical sensors to detect smoke
Software to ensure robust decision making
Electronics for configuration settings and status outputs
Power supply unit with back-up battery
Input terminals for Manual Activation Button and Door switch
RS485 communication bus to connect up to 8 systems to work as one system to protect larger
volumes up to 36 m3
User Interface with status LEDs, numerical display, push buttons and a key switch
Upon detection of a fire event, nitrogen gas is released from a Cool Gas Generator (CGG). The
nitrogen gas dilutes the oxygen level within the protected space, and consequently suppresses the
fire. This is in line with common practice using compressed IG-100, or other clean agents in Higher
Hazard Class A fires at 20
°
C. If Normal Class A fires are taken into consideration the systems can
protect a larger volume (see NFPA 2001 for the exact calculation)
EXX-750CNF
EXX-1500CNF
EXX-
2250CNF
1 generator
2 generators
3 generators
Gas mass
kg
0,9
1.8
2.7
L
750
1500
2250
Protection
m
3
1.5
3
4.5
ft
3
53
106
159
Table 1 Gas mass versus protected space (in normal conditions temperature and pressure)