EXXFIRE Installation and Service Manual 74
Extinguishing Gas Delay
When a fire event is registered, the Alarm status is set and the Alarm relay is closed. After the relay
has closed, there is a delay before the first gas generator is initiated. This delay can be set using DIP
switches 4 and 5.
The delay needs to be optimized to allow time for ventilation fans or air conditioning to reach a
standstill; thus, maximizing the effectiveness of nitrogen flooding (by avoiding further introduction of
fresh oxygen-rich air).
NB See Note 2 in section 5
Switch 4
Switch 5
Total Delay
0
0
Factory 0 s
0
1
5 s
1
0
10 s
1
1
15 s
Table 10 Gas Delay times