version 4.7.2 – July 10th, 2022 Firmware version V2.1.7 and higher
EXXFIRE Installation and Service Manual 31
How to clean spilt material
In case the CGG was not yet activated (i.e. a new CGG) and spilt:
• The grain material inside is highly toxic.
• The spilt material should be cleaned up according to the safety data sheet by trained
personnel following local guidelines and legislation.
In case the CGG was activated and then spilt:
• The material is a highly flammable solid and in contact with water releases flammable
gases which may ignite spontaneously.
• It is imperative that the spilt material does not come into contact with water. This could
lead to local poisoning of the environment, or personnel, and the release of toxic gas.
• The spilt material should be cleaned up according to the safety data sheet by trained
personnel following local guidelines and legislation.
• Typically, this may include evacuating the immediate area, and wearing gloves and a dust
mask while collecting the spilt material using a dry dustpan and brush.
Fire fighter instructions
• Use dry powder or sand to extinguish fire.
• Do not use water!
Wear self-contained breathing apparatus for firefighting if necessary.
Storage
• Conditions for safe storage: store in a dry, clean area, below 40 C.