Intended use
Safe operation of the EXXFIRE
®
750CNF/1500CNF/2250CNF is only guaranteed if used as
specified in this manual. Other forms of use can put persons at risk as well as the surroundings and
the environment.
During all phases of the lifecycle of the EXXFIRE
®
750CNF/1500CNF/2250CNF (e.g. transport,
deployment, etc.), standard Health, Safety and Environmental (HSE) procedures and regulations as
set forth by the product owner or local authorities must be adhered to, in addition to the specific
instructions in this document.
Misuse will occur when the EXXFIRE
®
750CNF/1500CNF/2250CNF is
used beyond its operational boundaries. Operational boundaries are
described in Chapter 2 and must never be exceeded.
Only personnel trained and qualified by the EXXFIRE Company may install, inspect and maintain the
product.
Disclaimer
It is the responsibility of the installer to ensure that the user is aware of the relevant contents of this
document and the documents listed herein. To ensure full system capabilities it is important to
check the following elements before installing the EXXFIRE systems:
1. Air tightness /leakage of the protected volume (e.g. cabinet). Gaseous fire protection works
only if the extinguishing gas can be kept inside the protected volume as long as possible to
prevent reignition
2. If in doubt the following precautions can be made; Close off all openings visible (cable
entries, ventilation etc.) with fire retardant material
3. Perform a functional test with an actual extinguishing to do an oxygen level measurement
for each cabinet type to ensure the proper design concentrations and hold time per
installation
4. If hold time is too low use EXXFIRE relay contact to switch OFF the Power to the cabinet, this
will prevent reignition also.