version 4.7.2 – July 10th, 2022 Firmware version V2.1.7 and higher
EXXFIRE Installation and Service Manual 105
operating manual). Incorrect handling or use of the product can cause serious damage and
unsafe situations (serious injuries and possible fatalities).
• If it’s necessary to enter in the flooding zone, wear self-contained breathing apparatus for
firefighting
• Ensure a good ventilation of the cabinet/server rack and the room before entering and
resuming operational functions safely
• The system must cool down for at least 4 hours.
• The CGG’s must be removed from the product and replaced with new ones.
• In case of a Used generator please ship them back to your local Distributor (see list on
website www.exxfire.com)
• Order a New and Unused generator and re-use the original packaging for shipping the Used
generator
• Take out the Unused generator from its UN certified packaging and install them in the EXXFIRE
fire protection system
• Take out the sticker for the return shipment of the Used generator and place them on the UN
certified box over the existing print
• Place the Used generator inside the packaging of the Unused one also using the plastic buffers
• Tape the lid of the box again fairly tight so it can’t
• Print the MSDS for the Used generator from our website
at https://exxfire.com/images/exxfire/MSDSExxFireUSEDGEN09N2.pdf
• Enclose the MSDS with transportation documents when shipping the generators back to the
Distributor
• In case there is no Distributor in your country please ship it back to EXXFIRE.