E145 27 732784 - Rev. A
ENGLISH
Display Advanced Function
Default
o1
OUT 1:
You can set the output OUT1 (open collector N.O.) in one of the following
functions:
00 = always active
0
1 = FAIL-SAFE
02 = INDICATOR LIGHT (off = closed; on = during opening and open/
in pause; flashing = during closing)
03 = COURTESY LIGHT (stays on for the duration of the movement
(even in SETUP) in addition to the set time of function
t1
04
= ACTIVE ERROR
05 = automated system OPEN or in PAUSE
06 = automated system CLOSED
07 = automated system MOVING
08 = automated system in EMERGENCY
09 = automated system in OPENING
10 = automated system in CLOSING
11 = DISABLED
12 = safety device ACTIVE
13 =
TRAFFIC LIGHT function (active when OPENING and with automated
system OPEN)
14 = timed output which can be activated from the second radio channel
OMNIDEC
(see function t1)
15 = output which can be activated from the second radio channel
OMNIDEC (step-by-step function)
16 = active during movement of leaf 1
17 = active during movement of leaf 2
If tr is displayed, it indicates that the output is used as a TIMER
set from the PC/MAC software.
00
t1
OUT 1 TIMING (visualised only with the function o1 = 03 or o1 = 14):
You can adjust the timing of OUT 1 output if a timed function has been selected
with a time from
1 to 59 minutes in 1-minute steps for functions 03-14 and
from
1 to 59 sec in 1-second steps for function 11
02
o2
OUT 2:
You can set the output OUT2 (open collector N.O.).
See the options as
o1.
02
t2
OUT 2 TIMING (visualised only with the function o2 = 03 or o2 = 14):
Adjustable as for
t1.
02