Alarm
12
If the value responsible for causing the alarm comes within the alarm limits again, the situation is
considered recovered and the alarm is no longer active. The siren automatically disables and the alarm
status changes into Alarm recovered. This message remains visible so you can see what caused the
alarm. Press to change the alarm status into Alarm temp. off followed by Alarm stand by.
If an alarm occurs the LED strip and the ‘menu selection and alarm bar’ will flash red. Perform the following
actions in case of a:
1. Press . The alarm overview displays the alarm status Alarm and shows the alarm message.
2. Press once more. The siren will temporarily go off and the alarm status changes to Alarm temp. off. The
alarm message remains visible to investigate what caused the problem.
3. Solve the alarm situation. When the alarm situation is solved the alarm status changes into Alarm stand by.
1. Press . The alarm overview displays the alarm status Alarm and shows the alarm message.
2. Solve the alarm situation.
3. Press once more. The alarm message will disappear and the alarm status changes into Alarm temp. off
followed by Alarm stand by.
If the alarm is disabled the control computer will not generate any alarm messages (except system
alarms). Never switch the alarm off during regular operation.
The alarm can be fully disabled, e.g. when the house is empty. Disable the alarm as follows:
1. Press .
2. Change the alarm status to Alarm disabled. The control computer will give a warning to indicate that the
entire alarm system has been disabled and will flash red.
Reactivate the alarm by changing the alarm status to Alarm stand by. The alarm message states that the alarm
has been disabled and is active again. The message will be cleared from the alarm overview.
Fancom advises testing the alarm weekly for correct functioning. During the test the control computer
will give a loud alarm.
Test the alarm as follows:
1. Press .
2. Change the alarm status to Alarm test. The LED strip and the ‘menu selection and alarm bar’ will flash red
and the control computer prepares an alarm message. The Alarm overview displays the alarm message.
3. Clear the alarm by pressing . The alarm status changes into Alarm stand by.