Setting how the alarm should be given with a DSR feedback alarm:
Loud alarm: report + alarm relay
Silent alarm: report only
No alarm: no alarm
Use options Combi position thru Combi air inlet to set the combi-table. At Combi position first enter the combi-
position (1..15) for which the settings are to be made. Then enter the required settings at Combi ventilation thru
Combi air inlet. If the positions are not used, set the combi-ventilation to 0%.
The combi-position chosen at Combi position will regularly appear on the display, when settings are made at
Combi ventilation thru Combi air inlet. When setting, for example, position 3 “C.3” will appear briefly. “Sta” will
appear when the actual combi values are read out.
Setting of the combi position: C.1 – C.15: indicate for which combi-positions settings
are to be made.
Setting of the combi ventilation percentage (Vent.) at which the fans must
activate/deactivate and air inlets position. The ventilation positions must increase
from C.1 – C.15. Set any unused positions to 0%.
Setting of the combi control part percentage at which the control computer must
control the controllable ventilation.