Installer settings
26
Analog output 1
Type
Setting if analog output 1 is used:
None
Air inlet combi 10-0V
Air inlet combi 0-10V
Heating 0-10V
Heating 10-0V
Thermal control 0-10V
Thermal control 10-0V
Vortex Pro/Natu 10-0V
Ventilation 10-0V
Ventilation 0-10V
Ventilation DSR 10-0V
Ventilation DSR 0-10V
ITM endstation 10-0V
If the Aura 14 controls the Fancom ProFlow system, assign Vortex Pro/Natu
10-0V and set Type triac to Ventilation.
Analog output 1
Correction factor
Setting of the correction factor. If there is a difference between the measured and the
control value (or between the output value and control value, if there is no feedback),
correction will take place. The extent of correction depends on the correction factor
(factor between 0.0 and 1.0). The higher the correction factor, the quicker correction
will take place; with a correction factor of 0.5, the computer will correct half the
difference each control time. With a factor of 1.0, the computer will correct the
difference in a single action.
Analog output 1
Control time(s)
Setting of the control time (seconds). The controller determines if controlling or
adjusting the 0-10V output is necessary at intervals equal to the set control time.