Installer settings
30
Combi relay
Setting of the relay to be switched, when the position set at C.1 is Active. The left field
indicates if relay 1 must switch on/off; the right field indicates this for relay 4.
Relay to be switched
Setting
None
0000
Relay 1
1000
Relay 1+2
1100
Relay 1+2+3
1110
Relay 1+2+3+4
1111
Relay 2
0100
Relay 3
0010
Relay 4
0001
Relay 1+3
1010
Relay 1+4
1001
Relay 2+3
0110
Relay 2+4
0101
Relay 1+2+4
1101
Relay 3+4
0011
Relay 1+3+4
1011
Relay 2+3+4
0111
Combi air inlet
Setting of the combi air inlet percentage at which the computer must control the air
inlet.
Combi damping
Setting of the speed of combi control (transitional positions) (Slow / Moderate / Fast).
Use slow and moderate if switching on additional fans is used, otherwise set to fast.
Ventilation calculation
type
Setting of the calculated and measured controllable ventilation and the calculated
total ventilation successively.
0: used with ventilation systems where the measured ventilation may not be
indicative for the total ventilation.
1: usually used with ventilation systems where fans are fully activated and the
controllable part reduced.