TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
23
During a system fault, dependent upon what caused the fault, all relays will be off, all zones will be powered
down, the zone, power fault and disabled LEDs will be on continuously. If any output is set to sounder then the
Sounder LED will also be on continuously.
To recover from this, the panel should be powered down for approximately 2 minutes and then re-powered. This
should be done by a competent person. If the panel appears to be operational, then a reset will clear the fault.
The only exception to this is the write enable switch. In access levels 1, 2A and 2B, if the switch is on, a system
fault will be indicated on the LEDs and display. The fault relay will be off (to indicate a fault condition). It has no
effect on the operation of the panel and serves as a reminder to the Engineer to switch off write enable before
leaving the panel.
If the display is blank and no LEDs are showing, then either the unit is not powered, or the mains has failed and
the batteries are lower than 21V. To recover from the low battery shut-off, power down completely and check
that the batteries are no lower than 21V and then power up the system.
If the batteries are lower than 21V then they should be replaced or monitored during initial charging to ensure
they recharge correctly. This could take several hours.
If the batteries are below 18V they should be replaced as they will have lost much of their capacity and are
unlikely to recover. This could leave the system with no power under mains fail conditions.
The alarm sounders have been activated.
The alarm sounders have been silenced whilst
operating, and the system is awaiting a reset.