TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
72
Control Panel Fuses and Protection
2 Zone Panel
4/8 Zone Panel
Zone output
300 mA trip polyfuse
Monitored Outputs 1 and 2
300 mA trip polyfuse
Auxiliary 24V DC supply
300 mA trip polyfuse
Mains
T4A Time Delayed 20mm Ceramic (in mains terminal block)
Battery Charger
300mA current limiter
Battery (reverse polarity)
3.15A F 20mm (in line with battery leads) Glass
Note: Refer to the relevant sections in the manual for full details of input and output ratings