TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
41
The Zone Status will display the current zone status of any zone
selected. These are displayed in text format and may be altered by
pressing the LEFT and RIGHT keys. Once the correct setting is
chosen press the ENTER key.
1. ON Zone is active.
2. OFF Zone is switched off.
The supply voltage to the selected
zone will also be switched off.
The Zone description will display the zone description for the selected
zone. These are displayed in text format and may be scrolled through
by pressing the LEFT and RIGHT keys. To change the text, highlight
the character to be changed and use the alphanumeric keypad to
change that character. After changing a character, the cursor will
automatically move to the next position. To confirm the changes press
ENTER.
This active control will allow the engineer to choose the type of
detectors that are to be used on the system. Use the LEFT and RIGHT
keys to toggle through the following options. Once the correct option
has been selected, press the ENTER key.
1. CP/DET Original style TWINFLEX
®
Multipoint.
2. CP/SM/HT New TWINFLEX
®
ASD Device.
This active control will allow the engineer to change the selected zone
type for ‘alarm confirmation’. Use the LEFT and RIGHT keys to toggle
through the following options. Once the correct option has been
selected, press the ENTER key.
1. COMM. Communal Zone Smoke detectors on
this zone will immediately activate all sounders
and outputs (subject to any other delays
programmed into the system).
2. DWELL Dwelling Zone Smoke detectors on
this zone will be subject to the ‘alarm confirmation
delay’ (for more information on this setting please
refer to the ‘alarm confirmation’ section).
6. Zones
1. Zone Status
6. Zones
2. Zone Description
6. Zones
3. Zone Mode
7. Alarm configuration
1. Set Zone Type
01/09/09 22:26 ENGR
ZONE STATUS (ON/OFF)
ENTER ZONE:00
Press Enter Key
01/09/09 22:26 ENGR
ZONE STATUS: OFF
1.ON 2.OFF
Press <> OR Esc Key
01/09/09 22:26 ENGR
ZONE NAMES
ENTER ZONE:00
Press Enter Key
01/09/09 22:26 ENGR
EDIT ZONE 01
NAME: ZONE 01
Press Enter Key
01/09/09 22:26 ENGR
ZN TYPE: CP/DET
1.CP/DET 2.CP/SM/HT
Press <> OR Esc Key
01/09/09 22:26 ENGR
SET ZONE TYPE
ENTER ZONE:00
Press Enter Key
01/09/09 22:26 ENGR
ZONE: COMMUNAL
1.COMM. 2.DWELL.
Press <> OR Esc Key