TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
55
There are up to 8 peripheral devices addressed 1 to 8 that can be
connected to a panel. When a peripheral device is enabled the panel
will monitor it and report it as missing if there is a cable break or loss of
communications.
The baud rate on the peripheral buss is fixed at 57,600 baud.
The Message rate is fixed at a 1 second update rate.
The printer functions are not currently in use.
Note: Ancillary equipment e.g. repeaters connected to the
peripheral bus do not meet EN 54-2 requirements.