TWINFLEX
®
pro² Control Panel Engineering and Commissioning Manual
55
There are up to 8 peripheral devices addressed 1 to 8 that can be
connected to a panel. When a peripheral device is enabled the panel
will monitor it and report it as missing if there is a cable break or loss of
communications.
The baud rate on the peripheral buss is fixed at 57,600 baud.
The Message rate is fixed at a 1 second update rate.
The printer functions are not currently in use.
11. Peripheral Buss
12. Printer
01/09/09 22:26 ENGR
1. PB RDU Supervise
1. PB Comm Configure
Press Enter Key
1. PB RDU Supervise
1. RDU 1 Supervise
RDU 1: Disabled
2. Disable 2. Enable
Press <> or Esc Key
2. PB Comm Configure
1. View PB Baud Rate
2. PB Comm Configure
2. View PB Mess Rate
Note: Ancillary equipment e.g. repeaters connected to the
peripheral bus do not meet EN 54-2 requirements.