0 Second post purge on operating control open.
15 Second post purge of flame fail during PTFI, Proving and MTFI.
Lockout on flame fail during PTFI, Proving and MTFI.
Relight operation on main flame fail.
Recycle operation on air flow failure.
Reset from lockout from pushbutton or line voltage.
Lockout on flame fail.
Lockout occurs if air flow terminal 6 is not proven 10 seconds into purge.
Modulate contacts on daughter board change state 1 second into Auto.
TYPE MEP397
PROGRAMMING SEQUENCE
L1/7
ON
PURGE
COMPLETE
FIRING
PERIOD
L1/7
OFF
7 SEC
PTFI
1 5 SECOND
PURGE
8
T
E
R
M
I
N
A
L
S
3
4
5
POST PURGE
INTERLOCK
AIR FLOW
PROVEN
5 SEC
PILOT
PROVING
5 SEC
MTFI
INTERRUPTED
PILOT
TYPE MEP696
PROGRAMMING SEQUENCE
L1/7
ON
PURGE
COMPLETE
FIRING
PERIOD
(AUTO)
L1/7
OFF
5/10 SEC
SELECTABLE
PTFI
30 SECOND
PURGE
8
T
E
R
M
I
N
A
L
S
3
4
5
SELECTABLE
POST PURGE
0/60 SEC
INTERLOCK
AIR FLOW
PROVEN
5 SEC
PILOT
PROVING
5 SEC
MTFI
INTERRUPTED
PILOT
MODULATE CONTACTS