Table 2: LOAD RATINGS: All Ratings are 120V, 60 Hz
Table 3: ALTERNATIVE LOAD RATINGS:
Table 4: COMPOSITION OF EACH COMBINATION
Fireye Terminal Typical Load Maximum Rating @120V 60 Hz
3 or 4
Individual or combined
Pilot valve(s)
Solenoid valve
Ignition Transformer
125 VA pilot duty (solenoid valve) plus
250 VA (Transformer)
5 Main Fuel Valve(s)
125 VA pilot duty (solenoid) or
25 VA pilot duty (solenoid) and
400 VA (opening) motorized, 250 VA hold
8 Motor or contactor
Terminal 8 rated to energize and de-energize 9.8 FLA,
58.8 LRA on safety lockout.
A Alarm
125 VA, pilot duty
Minimum load requirement = 100mA
COMBINATION NUMBER PILOT FUEL TERMINAL
3
IGNITION TERMINAL 4 MAIN VALVE TERMINAL
5
1 C
NO LOAD E
2 B
NO LOAD E
3 NO LOAD
NO LOAD E
4 E
A E
5 NO LOAD
A E
6 D
A E
7 D
A D
8 NO LOAD
A D
ABCDE
4.5A Ignition 50 VA Pilot Duty
plus 4.5A ignition
180 VA Ignition
plus motor val-
ues with: 600VA
inrush., 360 VA
open, 250 VA
hold
2A Pilot Duty 65 VA Pilot Duty
plus Motor valves
with: 3850 VA
in rush., 700 VA
open, 250 VA
hold