Seite/Page 164 - Kaptitel/Chapter 9: Tables 16.1.15
9.3 Cable cross section for vehicle generator
Fig. 9.3.0-1: Kabelquerschnitte/Cable cross sectiion
9.4 Coolant specifications
Use a mixture of water and antifreeze. The antifreeze needs to be suitable for aluminium. The antifreeze
concentration must be regularly checked in the interests of safety.
Panda PVK-UK 5000 LPE 20 40 8 8
Panda PVK-UK 6000 ND 20 40 8 8
Panda PVK-UK 6000i/8000i 20 40 8 8
Panda PVK-UK 8000 NE 25 40 8 8
Panda PVK-UK 9000 ND 25 40 8 8
Panda PVK-UK 12000 NE 25 40 8 8
Panda PVK-UK 14000 NE 25 40 8 8
Panda PVK-UK 15000 NE / 15000i 25 40 8 8
Panda PVK-UK 9-4 25 40 8 8
Panda PVK-UK 18 NE 25 40 8 8
Panda PVK-UK 24 NE 25 40 8 8
Panda PVK-UK 30 NE 25 40 8 8
Panda PVK-UK 35 YA 30 50 8 8
Panda PVK-UK 47 YA 30 60 8 8
Panda PVK-UK 60 MB 40 76 8 8
Panda PVK-UK 75 MB 40 76 8 8
Panda PVK-UK 100 MB 50 76 8 8
Wiring for vehicles.
single phase, not tin-plated, PVC-isolated.
nominal wire cross-section
[mm²]
allowed continous current (reference point)
a
a. DIN VDE 0298, part4.
at +30°C [A] at +50°C [A]
1 19 13,5
1,5 24 17,0
2,5 32 22,7
4 42 29,8
6 54 38,3
10 73 51,8
16 98 69,6
25 129 91,6
35 158 112
50 198 140
70 245 174
95 292 207
120 344 244
Generatortyp
Generator type
Kühlwasser
Cooling water
Abgas
Exhaust
Kraftstoff
Fuel
Zulauf
Feed
Rücklauf
Return