Inverter Panda PMGi 8000 / PMGi 10000
Seite/Page 208 - Kaptitel/Chapter 16: Inverter Panda PMGi 8000 / PMGi 10000 16.1.15
16.5 Settings for the use of iGenerators with power inverter
ATTENTION: Wrong settings can destroy the
PMGi
For the use of power inverter with the PMGi, the settings of
the power inverter must be modified.
Wrong settings can damage or destroy the PMGi.
The settings for the Victron power inverter must be adapted for the power inverters of other brands.
16.5.1 Settings in the Victron VE Configure II Software - General
Fig. 16.5.1-1: Settings in the Victron VE configure II Software
16.5.1.1 Uninterrupted AC power (UPS function)
Due to the fact that the power inverter connects the shore power immediately to the domestic grid (to fast), the PMGi
gets overloaded and shut down with an error.
UPS Function must be deactivated.
16.5.1.2 Dynamic current limiter
With inductive load the dynamic current limiter will raise up the Voltage in the DC circuit. These over voltage can
damage or destroy the PMGi.
Dynamic current limiter must be deactivated.