EasyManuals Logo

Fisher FIELDVUE DVC2000 User Manual

Fisher FIELDVUE DVC2000
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #15 background imageLoading...
Page #15 background image
Instruction Manual
D103176X012
Detailed Setup and Calibration
June 2017
15
Measured Variable Units and Ranges
Field Communicator Setup & Diag > Detailed Setup > Measured Var (1-2-4)
Follow the prompts on the Field Communicator to define the following measured variables units and ranges:
DAnalog In Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.
DInput Range Hi—Permits setting the Input Range High value. Input Range High should correspond to Travel Range
High, if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, Input Range
High corresponds to Travel Range Low. See figure 2‐1.
DInput Range Lo—Permits setting the Input Range Low value. Input Range Low should correspond to Travel Range
Low, if the Zero Control Signal is configured as closed. If the Zero Control Signal is configured as open, Input Range
Low corresponds to Travel Range High. See figure 2‐1.
DPressure Units—Defines the output and supply pressure units in either psi, bar, or kPa.
DLUI Pressure Units—Enter the pressure units displayed on the local user interface; psi, bar, or kPa.
DTemp Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the digital
valve controller's printed wiring board.
Figure 2‐1. Calibrated Travel to Analog Input Relationship
TRAVEL
RANGE
HIGH
TRAVEL
RANGE
LOW
THE SHAPE OF
THESE LINES DEPENDS ON
THE INPUT CHARACTERISTICS
LINEAR CHARACTERISTIC SHOWN
INPUT RANGE
LOW
INPUT RANGE
HIGH
ANALOG INPUT
MA OR % OF 4-20 MA
CALIBRATED TRAVEL, %
A6531-1
ZCS = CLOSED
ZCS = OPEN
NOTE:
ZCS = ZERO CONTROL SIGNAL

Table of Contents

Other manuals for Fisher FIELDVUE DVC2000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC2000 and is the answer not in the manual?

Fisher FIELDVUE DVC2000 Specifications

General IconGeneral
ManufacturerFisher
CategoryController
Device TypeDigital Valve Controller
Communication ProtocolHART
Input Signal4-20 mA
Enclosure RatingNEMA 4X, IP66
Operating Temperature-40 to 85°C (-40 to 185°F)
MaterialAluminum
Power SupplyLoop Powered
DiagnosticsAdvanced diagnostics
Output Signal4-20 mA
CertificationsATEX, IECEx, CSA, FM
MountingIntegral mounting to actuator

Related product manuals