7.7 Top-up, operation with the water treatment module
11-5
Wartung
Treatment
quantity reset
Perform action
Maintenance
Fig. FM.056.V01.15
8-2-1
Treatment
activate
edit mode?
Perform action
Top-up
Resetthetreatedquantity:
Requiredaftereachchangeofthe
treatmentmodule.Observeerror
messagenos.:55;61;31;page28.
Whenreset,thevalueineld4ofthe
operatingmenu[10]changesfrom
thepreviouslyprocessedquantityto:
00000 l
Caution:
Resettingto:00000lwithoutreplacing
themodule,andwithoutverifying
theresidualcapacity,leadstoan
unacceptablequalityofthetop-up
water!
Changingthetreatmentvolume
Requiredifthedefaultvalue(300litres)
doesnotmatchthecapacityoftheinitial
module,orthepresetvalueoftheused
moduledoesnotmatchthecapacity
ofthemodulechanged.(Impulsewater
counterstandard:10l/Imp.)
Caution:
Theuseofanincorrectvaluecanleadto
unacceptablequalityofthetop-upwater
orpreventtheuseremainingcapacities!
7.8 Malfunction messages
Proceduresandvaluesforerroridentication,evaluationandoutputhavebeentriedinpractice,preventsecondaryfailuresand
inviteuserawareness.Pleasenotethatincorrectset-upconditionscanleadtorepeatederrorsandinhibittheintendeduse.
Examplesofincorrectset-upconditionsare:incorrectornolongerapplicabledesign,outdatedequipment,incorrectinstallation
and inadmissible operational parameters.
Group error
message
menu line no.
Error, designation
cause; effect/action
Default
setting
Value Error message
number
- Voltagespikesensor(shortcircuit) ON 1
- Pressure sensor > 20 mA ON 2
Signaloutofsensorrangeorshortcircuit,nopressureread-
out;lockshieldvalvesinreturnconnectioninincorrectposition
/checkelectricalinstallation,threadedroundconnector,sensor
range(4-20mA;16bar),returnconnection,changesensorif
necessary
»service;Erroroff:self-resettingwhenerrorresolved.
- Pressure sensor < 4 mA ON 3
Signalbelowsensorrangeornotconnected,nopressureread-
out/checkelectricalinstallation,threadedroundconnector,
sensorrange(4-20mA;16bar),changesensorifnecessary»
service;Erroroff:self-resettingwhenerrorresolved.
- Volume sensor > 20 mA ON 4
Signaloutofsensorrangeorshortcircuit,novolumereadout/
checkelectricalinstallation,threadedroundconnector,sensor
range(FSI1:150-300;2:400-800;3:1000-2000;4:2500-5000;
5:6500-10000),changesensorifnecessary»service;ErrorOFF:
self-resettingwhenerrorresolved.
- Volume sensor < 4 mA ON 5
Signaloutofsensorrangeornotconnected,novolumeread-
out/checkelectricalinstallation,threadedroundconnectoror
sensorrange;changesensorifnecessary»service;ErrorOFF:
self-resettingwhenerrorresolved.