34
Group error
message
menu line no.
Error, designation
cause; effect/action
Default
setting
Value Error message
number
8-4- 12 Maintain. 1 OFF
Carryoutmaintainance1(equipmentservice) 365d 56
8-4- 13 Maintain. 2 OFF
Carryoutmaintainance2(inspectvesselinternally) 1825d 57
8-4- 14 Maintain. 3 OFF
Carryoutmaintainance3(inspectvesselstrength) 3650d 58
8-4- 15 (Maintain. 4) OFF
Carryoutmaintainance4(routineelectronicinstallation
inspection)
584d 59
8-4- 16 Date/ time invalid
Backuppowerfordate,timeistoosmall,notavailableor
incorrectlineentryofthesedata/redoorcompleteentryor
whenaftercompleteentryerrorrecurs»serviceErrorOFF;error
isself-resettingafterresolving.
OFF 53
8-4- 17 SPCx-hw: Phase monitor (option)
Phaseismissingorphasesequenceisincorrect,motorsand
valvesareturnedoff,nopressureincreaseorreduction;note:
theequipmentsuppliedisinstalledforoperationwithclockwise
rotatingeld(U/L1;V/L2;W/L3)/locatephases,checkpower
supplyfuseforthisequipment,switchwiringforcorrect
sequence;ErrorOFF,errorisself-resettingafterresolving.
OFF 30
7.9 Restarting
After long periods of downtime:
Ifthisdowntimewasplannedorscheduled,turnOFFthecontrolunitandcloseoffthelockshieldvalvestothesystemand
theisolatingvalvetothetop-upline.Afterthatdecompressandthendrainthewaterarea.Werecommendyoucarryout
maintenancebeforerestarting(seeMaintenancesection).
Usethecommissioningrecordsforrestartingandcheckespeciallyforsystemchangesthatcanleadtootheroperating
conditionsoftheexpansionautomat(e.g.systempressure).
If the power supply has failed:
Thetargetparametersanddefaultsettingsforpressure,aerationandtop-upwillremainunchanged,meaningautomatic
operationwillresumeautomaticallywhenpowerisrestored(controlunitON).Extraordinarysystemoperatingconditions(e.g.
coolingtobelowthedefaultsetting)mayfalloutsidethepermittedsettingsoftheexpansionvessel.
Caution:pleaseensurethatwhenthesystemcoolsdownorwarmsup,theminimumormaximumsystempressuredoesnot
exceedorfallbelowthepermittedoperatingpressure.Under-andover-pressuresafetyforoperationofheatingorcooling
systemsarenotwithinthestandardscopeofsupplyoftheFlamcomat.
Checktheautomat’soperationoncepowersupplyhasbeenrestoredand,ifnecessary,settheactualdateandtimevalues
(overviewmenuoptions).