33
Group error
message
menu line no.
Error, designation
cause; effect/action
Default
setting
Value Error message
number
8-4- 9 Top-up (optional) OFF
Top-upwatervolumetoolow(pulsewatermeter,option).
No impulse from impulse water meter after top-up
request;valve3,motor3areswitchedOFF,
feedpressuretoolow,valveinincorrectposition
ornotfunctioningproperly,motor3withinsufcient
ornopumpcapacity;exception:Signalline
isnotinstalledorismissing,watermeterswithoutfunction/
checkelectricalinstallation,checkcomponentfunctions,ensure
feed
conditions;
ErrorOFFoffafter,whenerrorisresolvedandreset.
22
Top-up without request (impulse water meter, option)
Impulsereceivedfromimpulsewatermeterwithoutrequestfor
top-up,valve3,motor3areswitchedOFF;equipmentinow
directionafterthewatermeterorvalve3isleakingorfailsto
close(incorrectowdirectionduetocheckvalveblocking)/
checkfunctioningandcheckforleaksintheequipment;
ErrorOFFoffafter,whenerrorisresolvedandreset.
23
Minimumcycledistanceexceeded 24
Maximumno.ofcyclespertimeframeexceeded 25
Maximumtop-upcycleamountexceeded
(impulsewatermeter,optional)
26
Maximumtop-upcycletimeexceeded 27
8-4- 10 Overow spill (optional) OFF
Drainingamounttoolow(impulsewatermeter,optional).No
impulsefromimpulsewatermeterafterdrainingrequest;valve
3.1,motor3.1areswitchedOFF,feedpressuretoolow,valve
inincorrectpositionornotfunctioningproperly,motor3.1with
insufcientordefectivepumpcapacity;Exception:Signallineis
notinstalledorismissing,watermeterwithoutfunction/check
electricalinstallation,checkcomponentfunction,ensurefeed
conditions;
ErrorOFFoffafter,whenerrorisresolvedandreset.
28
Drainagewithoutrequest(impulsewatermeter,option)
Impulsereceivedfromimpulsewatermeterwithoutrequestfor
drainage,valve3.1,motor3.1areswitchedOFF;
equipmentininowdirectiondownstreamofthewatermeter
or
valve3.1isleakingorfailstoclose(incorrectowdirectiondue
tocheckvalve
blocking)/checkfunctioningand
checkforleaksintheequipment;
ErrorOFFoffafter,whenerrorisresolvedandreset.
29
8-4- 11 Treatment (optional) OFF
Firstmessage(warning),70%ofthetreatmentvolumeentered
inthemenuhasbeenreached.
Preparereplacementmodule!Reseterrormessage.
70% 55
Secondmessage(warning),90%ofthetreatmentvolume
enteredinthemenuhasbeenreached.Thismessagereplaces
therstmessage,ifno.55hasnotbeenreset.Thevalueonthe
displayisinvertedandashes.Preparereplacementmodule!
(ifnecessary,replacemodule,observeerrormessageno.:31)
90% 61
Thirdmessage(warning),100%ofthetreatmentvolumeentered
inthemenuhasbeenreached.Thismessagereplacestherst
message,ifno.61hasnotbeenreset.Thevalueonthedisplay
isinverted;top-upisinterrupted.
May be followed by error no. 19. To maintain
thepressure(pressureincrease),replacethemodule,
resetthevalue,andthen,ifnecessary,modifytheentryfor
possibletreatmentvolume,seepage32.
100% 31
ENG