EasyManua.ls Logo

Flowserve Logix 3200MD Plus - ELECTRICAL CONNECTIONS; ELECTRICAL TERMINALS; COMMAND INPUT (4-20 MA) CONNECTION; COMPLIANCE VOLTAGE

Flowserve Logix 3200MD Plus
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Logix
®
3200MD+ Digital Positioners FCD LGENIM0110-0 05/16
flowserve.com 23
20 ELECTRICAL CONNECTIONS
20.1 Electrical Terminals
20.2 Command Input (4-20 mA)
Connection
The Logix
®
3200MD+ is reverse polarity protected,
however, verify polarity when making field termination
connection. Wire 4-20 mA current source to the input
terminal labeled “HART 4-20mA INPUT”. Tighten using 0.5
to 0.6 Nm torque. See Error! Reference source not
found.. Depending on the current source, a HART filter
may be required. See 28.1 Troubleshooting Guide.
20.2.1 Compliance Voltage
Output compliance voltage refers to the voltage limit the
current source can provide. A current loop system consists
of the current source, wiring resistance, barrier resistance
(if present), and the Logix
®
3200MD+ impedance.
The Logix
®
3200MD+ requires that the current loop system
allow for a 10 VDC drop across the positioner at maximum
loop current. The operating current range is from 3.9 to 24
mA.
In order to determine if the loop will support the Logix
®
3200MD+, perform the calculation in the following equation.
The Available Voltage must be greater than 10VDC in
order to support the Logix
®
3200MD+. Also, see Table 1:
Input Signal.
Equation 1
 
󰇛


󰇜


󰇛


󰇜







  
󰇛
 
󰇜
 
The available voltage (12.5 V) is greater than the required
voltage (10.0 V) therefore; this system will support the
Logix
®
3200MD+. The Logix
®
3200MD+ has an input
resistance equivalent to 500 Ω at a 20 mA input current.
CAUTION: The current must always be limited for 4-
20 mA operation. Never connect a voltage source directly
across the Logix
®
3200MD+ terminals. This could cause
permanent circuit board damage.
Figure 18: Terminal Diagram

Table of Contents

Related product manuals