Fluke 1730/BASIC - Accuracy at Reference Conditions

Fluke 1730/BASIC
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Energy Logger
Specifications
49
Accuracy at Reference Conditions
Parameter Range Resolution
Intrinsic Accuracy at Reference Conditions
(% of Reading + % of Range)
Voltage
1000 V 0.1 V ±(0.2 % of rdg. + 0.01%)
Direct Input
Rogowski Mode
15 mV 0.01 mV ±(0.3 % + 0.02 %)
150 mV 0.1 mV ±(0.3 % + 0.02 %)
Clamp Mode
50 mV 0.01 mV ±(0.2 % + 0.02 %)
500 mV 0.1 mV ±(0.2 % + 0.02 %)
1500 A iFlex
150 A 0.1 A ±(1 % + 0.02 %)
1500 A 1 A ±(1 % + 0.02 %)
3000 A iFlex
300 A 1 A ±(1 % + 0.03 %)
3000 A 10 A ±(1 % + 0.03 %)
6000 A iFlex
600 A 1 A ±(1.5 % + 0.03 %)
6000 A 10 A ±(1.5 % + 0.03 %)
40 A
4 A 1 mA ±(0.7 % + 0.02 %)
40 A 10 mA
±(0.7 % + 0.02 %)
Frequency
42.5 Hz to 69 Hz 0.01 Hz ±0.1 %
Aux Input
±10 Vdc 0.01 V ±(0.2 % + 0.02 %)
Voltage Min/Max
1000 V 0.1 V ±(1 % + 0.1 %)
Current Min/Max
defined by accessory defined by accessory ±(5 % + 0.2 %)
THD on Voltage 1000 % 0.1 % ±(2.5 % + 0.05 %)
THD on Current 1000 % 0.1 % ±(2.5 % + 0.05 %)
Power Factor
0 PF 1
0.01 ±0.025
Cosφ/DPF
0 Cosφ 1
0.01 ±0.025