Power Logger
Measuring Functions
23
Split Phase
For Split Phase, the Neutral is center-tapped and there are two hot legs which
correspond to A and B test Leads. AB is the voltage from phase to phase,
which is twice that of each individual hot leg. Refer to Figure 6 and connect
the leads as follows:
Voltage:
Network Test Leads
Line 1 A (L1)
Line 2 B (L2)
Line 1 C (L3)
N N
Current:
Network Test
Leads
A (L1) A (L1)
B(L2) Line 1 B (L2)
Not connected Neutral C(L3)
N N